You cannot have two or more of the same thresholds configured for the same element. Only one of these thresholds will trigger an alarm notification. Iris will fire for one threshold's warning and then the same threshold's critical.


Here is an example of when two thresholds for the same element can be set and notifications will be sent for both.


1. Threshold criteria latency 5 min average > 4.1      - send a notification to email address A

2. Threshold criteria latency 5 min average > 5         - send a notification to email address B


What you can do there is configure a single threshold:


1. where the warning ceiling triggers at >4.1

2. where the critical ceiling triggers at >5


Then configure two alarm notifications and two notification groups:


1. First alarm notification will send a notification to email address A when the threshold reaches a level of warning.

2. Second alarm notification will send a notification to email address B when the threshold reaches a level of critical.